+86 0573 86668515
EN  /  CN
TD50M NON-MID

Max.100A Direct Input

Measurements: V,A,W,Var,kWh,kVarh,PF, THD...

Bidirectional Energy and Power Measurement

Pulse Output

Communication: RS485 Modbus RTU/DLT645-2007

Networks:1P2W/2P3W/3P3W/3P4W

CE/ROHS Approved


Related Suggestion

TD50M series are three phase multifunctional energy meter to measure and analyze the most important electrical parameters, including voltage, current, four-quadrant power parameters, power factor, total harmonic, and etc. And it can also read a variety of energy parameters, involving bidirectional active and reactive energy, and so on. The series realizes the measurement and analysis of power parameters in various power grid environments, such as 1P2W, 3P3W and 3P4W.


The TD50M series have RS485 communication interface with highest baudrate 38400bps, supporting Modbus or DLT645 protocol for remote reading.


At the same time, the large-screen LCD and touch buttons help users to view and set various measurement parameters on site. 

Password protection function is added to greatly improve the data security.


Product Detials
Electrical Specifications
AccuracyVoltage/CurrentClass 0.5, Refer to IEC 61557-12
Active PowerClass 1 / Class 0.5, Refer to IEC 61557-12
Reactive PowerClass 2, Refer to IEC 61557-12
Apparent PowerClass 1, Refer to IEC 61557-12
Active EnergyClass 1 / Class 0.5S, Refer to IEC 62053-21/22, IEC 61557-12
Reactive EnergyClass 2, Refer to IEC 62053-23; Class 2, Refer to IEC 61557-12
Power FactorClass 1, Refer to IEC 61557-12
FrequencyClass 0.2, Refer to IEC 61557-12
Data Upgrading Rate1s (Optional: 100ms)
Voltage InputRated Voltage3x230VAC(L-N)/400VAC(L-L)
Voltage InputMeasurement Range:85 ~ 276 VAC(L-N),85 ~ 480 VAC(L-L)
Frequency45 ~ 65 Hz
Overload Capacity2x Rated Voltage by lasting 1s
Current InputCurrent Input0.15 ~ 100 A, Rated 5A
Overload Capacity30x Max. Current by lasting 0.01s
Pulse OutputPulse TypeOpen collector optocoupler
Pulse ConstantConfiguration: 400(Default), 100, 10, 1 imp/kWh(kvarh)
Pulse WidthConfiguration: 60, 100(Default), 200ms
Pulse Output TypeConfiguration: Import/Export/Total active/Total Reactive kWh
ClassClass A, Refer to IEC 62053-31
Voltage Input5 ~ 27 VDC
Pulse LightPulse constant: 400imp/kWh
Power Consumption ClassSelf-Consumption
Per Phase
Voltage Circuit: <2W/10VA;
Current Circuit: <1VA




Communication Specifications
Interface and Protocol2-Wire RS485; Modbus RTU(Default), DL/T645-2007(Optional)
Baudrate1200, 2400, 4800, 9600(Default), 19200, 38400 bps
ParityNone(Default), Even, Odd
Stop Bit1(Default), 2
Response Time<100ms
Bus TypeSemi-duplex
DistanceMax. 1000m
Bus LoadMax. 64pcs


Environment Specifications
Operation Temperature-25 ~ +55
Storage Temperature-40 ~ +80
Humidity<90%, no condensing
Pollution Degree2
Altitude<2000m
Vibration FrequencyRange: 10~150Hz, Refer to IEC 60068-2-6


Application Scenario
Our products are widely used in power, energy, industry, construction and many other fields.

Do you have questions about our products?

Please contact us:

Contact

Building 2, No.211, Yanbei Rd, Jiaxing, Zhejiang, China

+86 13706586937(Overseas)

Emily.Zhang@Rayfull.com.cn

15068363717(Chinese Market)

Tyrone.Gu@Rayfull.com.cn

+86 0573 86668515